Technical | NRCA technical bulletins and Special Reports | Special Reports |
Special Report: Considerations Pertaining to Polyisocyanurate Insulation
May 1999
Since the current generation of blowing agents for manufacturing polyisocyanurate insulation was introduced
into the U.S. roofing industry, the National Roofing Contractors Association (NRCA) has received a significant
number of reports about problems associated with polyisocyanurate insulation used in low-slope roof
assemblies. A majority of these problems involve polyisocyanurate insulation used as a component of single-ply membrane roof systems. However, NRCA does not believe the problems reported are limited solely to
single-ply membrane roof systems. Cover-board insulation, which frequently is used over polyisocyanurate
insulation in bituminous membrane roof systems, may mask some polyisocyanurate insulation problems in
built-up and polymer modified bitumen sheet membrane roof systems.
By issuing this report, NRCA does not mean to imply that polyisocyanurate insulation is problematic
or the reported problems are widespread in the industry. However, when these problems do occur, they
typically are noticed some time after the roof membrane is installed. As a result, correcting these problems
can be difficult and costly, often resulting in roof membrane removal and replacement. NRCA's intention with
this report is to notify the roofing industry of the reported problems with polyisocyanurate insulation and
disseminate information NRCA has received from roofing contractors and product manufacturers. This
information may be beneficial to roofing-industry professionals who encounter similar problems.
NRCA recognizes there are considerable shortcomings in the U.S. material standard for polyisocyanurate
insulation, American Society for Testing and Materials (ASTM) Standard C1289-95 titled "Standard
Specification for Faced Rigid Cellular Polyisocyanurate Thermal Insulation." This standard does not address
the need for manufacturers to adequately cure products prior to shipment and, in NRCA's opinion, the
standard's values for compression strength, dimensional stability and facer-sheet adhesion of finished
products are not adequate to assure roof system performance.
Until this standard is appropriately revised, NRCA recommends that polyisocyanurate insulation
manufacturers and designers who specify polyisocyanurate insulation implement the interim recommendations
in this report. These recommendations are intended to minimize problems that may occur on future low-slope
roofing projects.
Types of Problems
Some problems with polyisocyanurate insulation initially occurred in late 1993 and early 1994 when
manufacturers were required to change their products' blowing agent component. Prior to January 1994,
almost all polyisocyanurate insulation manufacturers used a blowing agent (CFC-11) that contained
chlorofluorocarbons. CFC-11 was determined to be harmful to the earth's ozone layer, and government
regulations were implemented that required manufacturers to change the blowing agent. This change
introduced new variables into the product's manufacturing and took some time to perfect; however, it is
doubtful that any of the current reported problems with polyisocyanurate insulation are from this transition in
blowing agents.
Many problems currently observed in the field are related to an improper mix ratio of the foam's components,
which is a manufacturing defect. Polyisocyanurate insulation is manufactured from two primary components,
referred to as A and B components. The A component is isocyanate; the B component consists of polyol,
catalysts, additives and the blowing agent(s). In the manufacturing process, A and B components must be
combined in precise quantities to achieve the desired chemical reaction that creates proper foam cell
structure. Off-ratio component mixing can result in foam cells that are elongated rather than properly spherical
or foam that is too soft or brittle.
The following is a discussion of some of the reported problems experienced with polyisocyanurate insulation.
- Facer-Sheet Delamination: Facer-sheet delamination is the separation of the facer sheet, which is
typically a glass fiber or asphalt felt, from the polyisocyanurate foam core. This can be the result of the
manufacturing process where the foam is off proper ratio, resulting in foam that is too soft or elongated
foam cells that are directly adjacent to the facer sheet. Elongated cells are not as strong as spherical
cells and can cause crushed or powdered foam when subjected to minor surface loads (e.g., normal
installation traffic). Off-ratio foam and elongated foam cell structure are manufacturing defects.
Facer-sheet delamination sometimes is found when there is excessive traffic (e.g., heavy equipment
traffic) over the insulation's surface. Facer delamination caused by excessive traffic typically will exhibit
crushed cells immediately below the interface between the foam and facer sheet. When facer-sheet
delamination is caused by excessive traffic, the affected area generally will be limited to the traffic areas
only, rather than other large portions of the roof.
- Edge Cavitation: Board-edge cavitation is a condition in which the exterior edges of individual boards
exhibit concave depressions. Edge cavitation is a manufacturing defect that once was associated most
frequently with the change in blowing agent; however, it still is reported occasionally.
Currently, edge cavitation is caused most often when a minor amount of water is used as an ingredient
in the manufacturing process. Small amounts of water sometimes are added during the product's
manufacturing to generate carbon dioxide as a co-blowing agent. The carbon dioxide can be useful in
improving some of the foam's physical properties. When changes first were made in the blowing agent,
it was not known that the new blowing agent (HCFC 141b) had a greater tendency to dissolve in the
foam's polymer matrix than the older blowing agent (CFC-11). If a significant amount of the blowing
agent dissolves into the cell walls, the walls are weakened.
Also, the chemical reaction between the A and B components produces heat, with the temperature
within the foam reaching as high as 300 F (149 C) during manufacturing and curing. The high reaction
temperatures cause the gas pressure within the cells to be less than the ambient atmospheric pressure
when the product cools. If carbon dioxide is present (e.g., the result of using a small amount of water
in the process), the carbon dioxide will diffuse out of the cells faster than the air components diffuse into
the cells, magnifying the pressure differential between the foam cells and environment.
The combination of weakened cell walls and great pressure differential creates elongated cells too weak
for the board's thickness. This occurs most rapidly at the board's edges, resulting in poor foam structure
and board-edge cavitation.
- Cupping or Bowing: Board cupping or bowing can be caused by an off-ratio mix, a manufacturing
defect, that creates distorted cell structures to be distributed unevenly within the foam's thickness. The
uneven distribution of the cells creates inherent dimensional instability and will exhibit substantially
different compressive strength values in the board's length, width and thickness directions. When
placed under load, the board will resist the load differently, resulting in cupping or bowing.
Cupping or bowing also can occur when one of the board's sides gets wet. As it dries, the board's side
shrinks, which exerts unbalanced forces within of the board. This causes the board to become concave.
Condensation can occur within the insulation's packaging, which allows the top board in a bundle to
become wet on its top surface. The top surface of the top board in a bundle also can become wet if the
insulation is not properly protected from precipitation (e.g., rain). When this happens, the boards may
become cupped.
Cupping of boards as a result of them becoming wet typically is the result of inadequate packaging of
the insulation bundles, which can be considered a manufacturing defect, or inadequate material
handling, storage or application, which may be application problems. The cupped boards as a result
of wetness generally will appear in random locations throughout the roof. It would be rare for all the
boards in any bundle of insulation to have only their top surfaces wet.
- Shrinkage: Board shrinkage generally is associated with an off-ratio foam mix, which is a
manufacturing defect. However, ASTM C1289 allows up to a 4 percent linear change. This linear
change value represents the product's dimensional stability when conditioned at 158 F (70 C) and
97 percent relative humidity for seven days.
When applying this 4 percent value to a 4-foot by 8-foot (1.2-m by 2.4-m) polyisocyanurate insulation
board, it can be interpreted that the long dimension is allowed to shrink or expand up to 3.8 inches
(98 mm) and still be in compliance with the ASTM standard. As a result of this high allowable
dimensional stability value, board joints installed tightly butted can be found with wide gaps, which can
impact roof system performance.
- Crushing or Powdering: Board crushing or powdering sometimes is attributable to foam crushing or
powdering from an off-ratio mix that is too rich in isocyanate, resulting in foam that is too brittle. Even
minor loads (e.g., normal installation traffic) on the insulation's surface can crush the foam and turn it
to powder. This also can cause the facer sheet to delaminate from the foam core. This is a
manufacturing defect.
Crushing or powdering also can be caused by excessive traffic (e.g., heavy equipment) over the
insulation's or membrane's surface. This condition generally is not a manufacturing defect and usually
will be confined only to high traffic areas, rather than other large portions of the roof.
Interim Recommendations
Until ASTM C1289-95 is revised to address the manufacturing problems reported or some other appropriate
material standard is developed for use in the United States, NRCA recommends that polyisocyanurate
insulation used in low-slope roof assemblies be manufactured to the following criteria.
- Compressive strength: 23 pounds per square inch (158 kPa) minimum.
- Dimensional stability: 2 percent maximum linear change when conditioned at 158 F (70 C) and
97 percent relative humidity for seven days.
- Curing time: 24 hours minimum, plus an additional 24 hours minimum per inch (25 mm) of thickness,
at a minimum of 60 F (16 C) before shipment from the manufacturer.
- Board thickness: 2 inches (51 mm) maximum.
Also, as indicated in The NRCA Roofing and Waterproofing Manual, Fourth Edition, roof system
manufacturers and designers who specify polyisocyanurate insulation in their designs are urged to incorporate
the following criteria.
- Board size: 4-foot by 8-foot (1.2-m by 2.4-m) maximum board size for loose-laid and mechanically
attached insulation boards, 4-foot by 4-foot (1.2-m by 1.2-m) maximum board size for insulation boards
adhered to a substrate.
- Board thickness: 2 inches (51 mm) maximum; when thicker total thicknesses are necessary, specify
insulation boards in multiple layers to achieve the desired total thickness. When multiple insulation
layers are used, the insulation board's joints in the top layer should be staggered vertically and offset
from the joints in the underlaying layer(s).
|
 |
|